Luminaries

  • Type of Protection: Flameproof (Explosion proof) Ex-d or Increased Safety Ex-e
  • Area Classification: Zone 1 & 2 or Zone 2
  • IP Protection: Minimum IP 55 or IP 65/66
  • Apparatus standard: For Ex-d – IS 2148/1981 and Ex-e IS 6381/1972 & IS 8224/1976 (Recertification based on IEC 60079 series is under process)
  • Material: Cast Aluminium Alloy LM-6
  • Finish: Corrosion Resistant Epoxy paint Shade 631 of IS 5
  • Glass: Heat and Impact Resistance and Toughened Glass TYPE “A”. Make – Dome Glass for Well glass fitting – BOROSIL
  • Wire Guard: Mild Steel Plated & Powder Coated of 3 or 5 mm Dia
  • Gasket: Endless Neoprene minimum 3 mm dia
  • Hardware: All flame path – SS Allen Bolt or Threaded. All other SS
  • Reflector: Alluminium Anodized
  • Mounting: Different for different type of fitting
  • Voltage: 230V 50 Hz AC
  • Lamp Holder: Based on Lamp Type like 2Pin / 3Pin / ES27 / ES40 / Bi pin or suitable for various PLL / CFL lamp, Cable Entry Size / No.: 3/4″ BSCon. / 2
  • Earthing: External 2 Nos. of size M6 & Internal 1 No. of size M6, Wire Size: As per lamp rating minimum 1.5 sq. mm. Cu flexible Fiber Glass Insulated
  • Accessories: (OPTIONAL) Lamp, Cable Gland & Stopping Plug, External Reflector, Mounting Hardware